COMMERCIAL PRODUCTSPotential for Fire, Smoke and Asphyxiation HazardsTo the Homeowner or Equipment Owner:Please read and carefully follow all instruct
10Special Note: The burner is shipped with a by-pass plug installed in the fuel unit. For low/high operation, the by-pass plug must be left in the fue
11CF1400/CF2300 Burner ManualLow-fi re/high-fi re operation – The fuel unit nozzle port pressure is factory set at 300 psig.At high fi re, full pressure
1221356847StandbyMotor-off delayValve-on delayTrial forignitionIgnition carryoverRunLockoutRecycle9PumpprimeRun: With a fl ame established and the cont
13CF1400/CF2300 Burner ManualFigure 13 – Typical Wiring (7505P)Section: Wire the Burner
14Figure 14 – Typical Wiring (R7184B)Typical Burner Sequence of Operation - 7184B ControlRefer to the appliance manufacturer’s wiring diagram for actu
15CF1400/CF2300 Burner ManualPrepare the Burner for Start-upStart-up checklistVerify the following before attempting to start burner.Combustion air su
16Figure 16 – Adjusting Plate Initial Setting, TypicalTable 4A – CF1400 Initial Indicator Adjustment Plate SettingsCF1400TubeHead Position Damper Posi
17CF1400/CF2300 Burner ManualInitial Air SettingsIf your burner was built for a specifi c OEM (Original Equipment Manufacturer) application, the “Mfr’s
18Start the BurnerStart Burner and Vent Air From Oil Line Disable FunctionAny time the motor is running, press and hold the reset button to disable t
19CF1400/CF2300 Burner ManualPlace the low-fi re hold switch in the high-fi re position. The damper motor will begin to rotate after four seconds.Use co
2Special Requirements - The installation of a burner shall be in accordance with the regulations of authorities having Jurisdiction.For recommended in
20Annual ServiceReplace the oil supply line fi lter. The line fi lter cartridge must be replaced to avoid contamination of the fuel unit and nozzle.Insp
21CF1400/CF2300 Burner ManualSK9930324561SK9931897Section: Replacement PartsFigure 19a – Burner Replacement Parts
22Item Part Name DescriptionCF1400 Part No.CF2300 Part No.1 Oil Valve Mounted on Junction Box 21789U 21789U2 Knurled Nut All models 3666 36663 Adjusti
23CF1400/CF2300 Burner ManualFigure 19b – Burner Replacement Parts (Continued)SK9936SK9932SK99301413121020112122231516171819
USA: P.O. Box 1289 ● Elyria, Ohio 44036Canada: R.W. Beckett Canada, Ltd. ● Unit #3, 430 Laird Road ● Guelph, Ontario N1G 3X7www.beckettcorp.comPart Nu
3CF1400/CF2300 Burner ManualOwner’s Responsibility:Service Agency Responsibility:Follow these instructions exactly.Failure to follow these instruction
4Pre-Installation ChecklistCombustion Air SupplyThe fuel supply piping and tank must provide #1 or #2 fuel oil at pressure or vacuum conditions suitab
5CF1400/CF2300 Burner ManualThe fuel unit nozzle port pressure is factory set at 300 psig. Some original equipment manufacturer burner applications ma
6ModelFiring Rate(gph)Minimum DimensionsRefractory Lined Wet-based BoilersHLHLCF1400 0 to 5 7.0” 25.0” 7.0” 25.0”5 to 10 8.0” 35.0” 8.0” 40.0”CF2300 5
7CF1400/CF2300 Burner ManualStray LightThe control must detect a dark, no-fl ame condition in order to start the burner or it will hold in the stray li
8Figure 5 – Nozzle and Nozzle Line AssemblyFigure 6 – Nozzle Line Assembly in BurnerMount Air Tube to BurnerRemove the rear access door from the back
9CF1400/CF2300 Burner ManualSet “Z” DimensionReplace the rear access door on the burner, making sure that the adjusting plate assembly is seated in th